To Study Three Phase Fully Controlled Bridge Converter.
S.No. | Apparatus/Software Used | Specification | Range/Rating | Quantity |
1 | ||||
2 | ||||
3 | ||||
4 | ||||
5 |
The figure ‘1’ shows the power circuit of three phase fully controlled converter. The load is fed via a three phase half wave connection to one of the three supply lines, no neutral being required. Hence transformer connection is optional. However, for isolation of output from supply source, or for higher output requirement, the transformer is to be connected. If transformer is used, then one winding is connected in delta because the delta connection gives the circulating path for third harmonic current. This circuit consists of two groups of SCRs, positive group and negative group. Here, Scr T1, T2, T3 forms a positive group. Whereas SCR T4, T5, T6 forms a negative group. The positive group SCRs are turned on when the supply voltages are poisitive and negative group SCRs are turned on when the supply voltage are negative
Continuous Conduction Mode:The firing angle of each phasor is varied through a range of 60 degree to 180degree. The minimum firing angle is 60degree and is taken as α=0, at 60degree. When the phasor R-Y is allowed to conduct at α between zero to, π/3 it continues to conduct by 60degree when the phasor R-B is fired. The condition is shifted from SCR T5 to SCR T6. T5 is commutated off by reverse voltage of phase Y and Y across it. The Phasor R-B conducts after another 600 after which it is replaced by phasor (Y-B) when phase Y voltage assumes greater value than B or R. Hence load current is continuous for between 0 to ;π/3 The waveforms are shown in figure.
Respective Gate wave should be connected respective MOSFET.
Get all latest content delivered to your email a few times a month.