To perform the Scott connection of transformer from three phases to two phase connection.
S.no | Equipment | Type | Range | Quantity |
1 | Voltmeter | MI | (0-300)V/(0-600)V | 2nos/2nos |
2 | Ammeter | MI | (0-5)A | 1nos |
3 | Connecting Wires | -- | ------ | Required |
Transformer Specifications:
Mains Transformer:
Transformer Rating :( in KVA) __3kVA__________
Winding Details:
LV (in Volts): ___150V______________________
LV side current:_______20A________________
HV (in Volts): ________230V________________
HV side Current:______13A________________
Type(Shell/Core):_____________________
Tapping’s: ___________0% , 50% , 100%_________________
Teaser Transformer
Transformer Rating :(in KVA) ______3kVA_____
Winding Details:
LV (in Volts): ___150V______________________
LV side current:_______20A________________
HV (in Volts): ________230V________________
HV side Current:______13A________________
Type(Shell/Core):_____________________
Tapping’s: ___________0%,86.6%_________________
3- ɸ Auto transformer Specifications:
Input voltage: ___415_________________(Volt)
Output Voltage : ____(0-470)_______________(Volt)
Frequency:________50________________(Hz)
3Current rating (in Amp):______8A per line__________
Procedure:
Calculations:
V2TM=√V22T+V22T
Tabular column:
S.no | Set1(L1, L2,L3,L4) | Set2(L1,L 2,L3,L4) | Input voltage(V1)(V) | Input curren tI1 (A) | Output current(A)/Teaser (IT1) (A) /Main(IM1)(A) | Output Voltage(V)/Teaser (V2T) (V) /Main(V2M) | Theoretical calculations V2TM= √(V2T) 2+(V2M) 2 | 1 | 0 | 0 | 415 | 0 | 0/0 | 230/230 | 320 | 2 | L1 | 0 | 415 | 0.3 | 0.8/0 | 230/230 | 320 | 3 | L1 | L2 | 415 | 0.35 | 0.8/0.8 | 230/230 | 320 | 4 | L1,L2 | L1 | 415 | 1 | 1.5/0.8 | 230/230 | 320 | 5 | L1,L2 | L1,L2 | 415 | 1 | 1.5/1.5 | 230/230 | 320 | 6 | L1,L2,L3 | L1,L2 | 415 | 1.4 | 2.4/1.5 | 230/230 | 320 | 7 | L1,L2,L3 | L1,L2,L3 | 415 | 1.4 | 2.4/2.4 | 230/230 | 320 | 8 | L1,L2,L3,L4 | L1,L2,L3 | 415 | 1.8 | 3/2.4 | 230/230 | 320 | 9 | L1,L2,L3,L4 | L1,L2,L3,L4 | 415 | 1.8 | 3/2.4 | 230/230 | 320 |
Result:Scott connection is performed on transformers and supply 3-Φ to 2- Φ conversion is observed.
Get all latest content delivered to your email a few times a month.